Useful Information
What’s ASY
13
Digital outputs
20
21
How to prevent the programming by key-pad
It is possible to prevent any access to
programming by keypad by modifying the
selector under the power supply slot (see
the drawing on the left), or closing the con-
tact number 1 of the digital input module,
when present.
The variables measured by the instrument are
correct if the polarities of the inputs have been
observed (as shown in the figure below); if not,
measuring and retransmission errors may
occur due to the wrong direction of the current flowing
in the primary / secondary of the connected current
transformer.
Setting Examples
Example 1 Analogue output: take the measure of a
power consumed up to 100kW, and retransmit it with a sig-
nal from 4 to 20 mA; the module to be used is AO1050 or
AO1026 (single or dual output from 0 to 20mA), the instru-
ment must be set as follows:
VAr: (variable), W (system active power)
LoE: (minimum electrical scale) 0.0 K; the K and M mul-
Selector: turn the selector with a little screwdriver.
- Free programming.
- Lock programming.