Hardware Functions
In-Out
Performances
The best to suit your needs!
Energy Meters EM1 DIN EM2 DIN/96
89x35mm
Mechanical
YES
N.A
5+1 DGT (0.1kW)
Class 2 (EN6036)
≤200ppm/°C
2
1-phase
230VAC
Ib:15A,
Imax: 22.5AAC
N.A.
N.A.
TRMS method
kWh
N.A.
1 (open collector)
N.A.
N.A.
N.A.
N.A.
Start up current
50mAAC
Self power supply
CE
IP40
Housing (H x W)
Display type
Variables on display
Instantaneous variables
Energy variables
Accuracy
Temperature drift
Sample/s
System type
Voltage inputs (Un)
Current inputs (In)
Digital inputs
Primary of CT/VT
Measurements:
Variables
Harmonic distortion
Outputs: Pulse
Alarm
Analogue
Serial
Digital filter (action)
Other characteristics
Power supply
Approvals
Protection degree
EM1 DIN, EM2 DIN, EM2 96, are energy meters suitable to
measure the consumed energy in various services and
light/medium industries. These instruments are normally
connected downstream the official watthours meter to
measure the energy consumed by machines or depart-
ments, in order to split the costs accordingly.
EM1 DIN is the electromechanical space-saving solution: in
only 2-DIN module housing there is a reliable active energy
meter with optional pulse output.
EM1/EM2 DIN EM2 96
Comm
Hardware Functions
In-Out
Performances
Comm
EM1 DIN
EM2 DIN/96
EM2 96 and EM2 DIN display the total and partial active
and reactive energy.
89x107/96x96mm
LCD back lighted
YES
N.A.
6 DGT
Class 1
≤200ppm/°C
3
Bal: 1-3-phase
Unbal: 3-phase
250/433VAC
5AAC
N.A.
CT:progr. up to
5000A
TRMS method
Total:kWh, kvarh
Partial:kWh, kvarh
N.A.
N.A.
Driven by RS485
N.A.
N.A.
N.A.
Only EM2 96:
modular concept,
plug-in modules
DC power supply
24,48,115,230VAC
96 only:18 to 60,
90 to 260VAC/DC
CE,-cURus, CSA (96)-
IP40 (DIN)
IP65 (96)
96
DIN
16