Specifications are subject to change without notice UDM35 DS ENG 261110 1
Multi-input modular instrument 3 1/2 DGT LED
0.1% RDG basic accuracy
TRMS AC current and voltage measurements
AC/DC current measurements: selectable full scales
(200µA to 5A)
AC/DC voltage measurements: selectable full scales
(200mV to 500V)
°C or °F temperature measurements
(Pt100-250-500-1000, Ni100, TC J-K-S-T-E)
Resistance measurements: selectable full scales
(20to 20k)
Dual rate, speed, frequency and period measurement
(0.001Hz to 50kHz)
Up to 4 independent alarm set-points (optional)
20mA/10VDC analog output (optional)
Serial port RS485 or RS232 (optional)
MODBUS, JBUS communication protocol
Product Description
µp-based digital panel
meter, 3 1/2 DGT LED indi-
cator, for current, voltage,
temperature, resistance,
rate, frequency, speed and
period measurements. Mea-
suring ranges and functions
easily programmable from
the key-pad or from the PC
by means of optional Udm-
Soft software. UDM
35
includes storage min-max
functions and double level
protection password.
Housing for panel mounting
with front protection degree:
IP67, NEMA12.
Digital Panel Meters
Modular Indicator and Controller
Type UDM35
Type Selection
Slot A (measuring inputs)
LSX:
signal inputs:
0.2-2-20mA DC/AC;
0.2-2-20V DC/AC
LSE/
LSF:
signal inputs: + AUX:
0.2-2-20mA DC/AC;
0.2-2-20V DC/AC
HSX: signal inputs:
0.2-2-5A DC/AC;
20-200-500V DC/AC
TRX: signal inputs: TC tem
-
perature probes (J-K-
S-T-E, Pt100-250-500-
1000) and resistance
(0.02-0.2-2-20k)
TF1: 0.001Hz to 50kHz for
DC signals: PNP
,
NPN, NAMUR, TTL,
free of voltage, con
-
tacts, voltages up to
14VDC
TF2: 0.001Hz to 50kHz for
AC signals: pick-up,
voltages up to
500VAC
Slot B (communication)
XX:
None
SX: Serial port RS485
SY: Serial port RS232
A
V(*):
Single analogue output,
0 to 20mA DC and
0 to 10V DC
Slot C (communication and alarm)
XX:
None
R1:
Single relay output,
(AC1-8AAC, 250VAC)
R2
: Dual r
elay output,
(AC1-8AAC, 250VAC)
R4
: Dual relay output,
(AC1-
8AAC, 250VAC)
+ dual
open collector output
(NPN, 100mA)
R5
: 4 relay outputs
(AC1-5AAC, 250VAC)
AV(*):
Single analogue output,
0 to 20mA DC
and
0 to 10V DC
Slot D (power supply)
H: 90 to 260V AC/DC
L:
18
to
60V
AC/DC
(24 to 48V AC/DC ±
25% according to UL)
3:
10
to
28V
DC
(12 to 24V DC ± 15%
according to UL)
Options
XX: None
TX: Tropicalization
Model
Slot A
Slot B
Slot C
Slot D
Options
How to order
UDM35 XXX XX XX X XX
Front protection degree: IP67, NEMA12
Linearization of Hz inputs up to 16 points
How to order
UdmSoft-kit
UdmSoft-kit: software plus communication cable for pro-
gramming UDM35 by means of PC.
UdmSoft: software for programming UDM35/40/60 by
means of PC, downloadable from www.carlogavazzi.com.
(*): The two analogue
outputs cannot be
used at the same
time. It is possible to
plug in only one
module by instru-
ment.
Vue de la page 0
1 2 3 4 5 6 ... 13 14

Résumé du contenu

Page 1 - Type UDM35

Specifications are subject to change without notice UDM35 DS ENG 261110 1•Multi-input modular instrument 3 1/2 DGT LED• 0.1% RDG basic accuracy•

Page 2 - Input specifications

10 Specifications are subject to change without notice UDM35 DS ENG 261110UDM35Temp. measur. from thermoresistanceTemp. measur. from thermocoupleRe

Page 3

Specifications are subject to change without notice UDM35 DS ENG 261110 11UDM35Auxiliary commandFig. 19BQ TF1Wiring diagrams (cont.)Max 500VACPick

Page 4 - 4 Specifications ar

12 Specifications are subject to change without notice UDM35 DS ENG 261110UDM35BO R4: dual relay output + dual open collector output: the load resi

Page 5 - Output specifications

Specifications are subject to change without notice UDM35 DS ENG 261110 13UDM35:-to program values;-to select functions;- to scroll display pages.

Page 6 - Supply Specifications

14 Specifications are subject to change without notice UDM35 DS ENG 261110UDM35BP LPower supply:18 to 60V AC/DCBO R4Dual relay output +Dual open co

Page 7 - General Specifications

2 Specifications are subject to change without notice UDM35 DS ENG 261110UDM35Analogue inputs Channels and variableBQ LSX module 1, mA and V DC/ACB

Page 8 - Used calculation formulas

Specifications are subject to change without notice UDM35 DS ENG 261110 3UDM35Module Inputs Type Accuracy Temp. drift Min. indication (<) Max.

Page 9 - Wiring diagrams

4 Specifications are subject to change without notice UDM35 DS ENG 261110UDM35Input impedances and overloads(*) Maximum measuring current generated

Page 10 - Wiring diagrams (cont.)

Specifications are subject to change without notice UDM35 DS ENG 261110 5UDM35RS422/RS485 (on request) Module: BR SXSerial output Bidirectional (s

Page 11

6 Specifications are subject to change without notice UDM35 DS ENG 261110UDM35Input engineering unit BQTFx only: programmable among Hz, kHz, rpm, k

Page 12 - RS1,2,3...N

Specifications are subject to change without notice UDM35 DS ENG 261110 7UDM35Safety StandardsSafety EN 61010-1, IEC 61010-1Connections Screw type

Page 13 - Engineering Units

8 Specifications are subject to change without notice UDM35 DS ENG 261110UDM35Available modules Possible module combinationsOnly for TRMS Measureme

Page 14 - 14 Specifications ar

Specifications are subject to change without notice UDM35 DS ENG 261110 9UDM35Wiring diagramsProcess signal wiring diagramsCurrent measurements4-w